Metering installations
This advisory note outlines common non-compliance issues found by Building Commission NSW inspectors in electrical metering installations.
| Note | 1/2018 |
| Date issued | July 2018 |
| Last updated | September 2018 |
| For | Licensees / Contractors / the Electrical Industry |
| Issued by | Building Commission NSW – Electrical Inspections Team |
| Scope | Applies to all of NSW |
Purpose
This advisory note outlines some common non-compliances found in electrical metering installations.
Reference
Service and Installation Rules 2025 and Metering Annexure July 2018
Common non-compliances found
Some of the common non-compliances found by Building Commission NSW inspectors are:
1. Marking of service equipment
- Service neutral link must be identified with complete wording. Abbreviations such as “Service N/L” and “Service N/Link” are not acceptable.
- Rating of Service Protection Devices/Meter Protection Devices (SPD/MPD) must be marked on meter, preferably below the SPD/MPD.
2. Fixing of metering equipment
- All fixing points of a meter are to be utilised.
- Bolts are not allowed to protrude, at the back of the meter panel, more than 5mm past the fixing nut.
- A non-conductive bolt must be used where the mounting bolt protrudes through the meter panel and can be contacted on the front of the panel.
3. Earthing
- If the Multiple Earthed Neutral (MEN) connection is at the service neutral link it must be moved to the customers neutral link.
4. Sealing
- Sealing of the meter terminal cover, service neutral link and escutcheon plate of the SPD/MPD is required to be carried out.
Building Commission NSW acknowledges that seals may be broken between the time the work is completed and the time the inspections are undertaken. Non-compliances are issued for metering equipment not being sealed for two purposes:
- To ensure the metering equipment gets resealed
- For the installer to provide information to the Metering Provider so that they may check that meter has not been tampered with.
General information
HRC fuse assemblies
Building Commission NSW has noticed a number of high rupturing capacity (HRC) fuse assemblies being used for meter and service protection devices which do not comply with the requirements of the SIR.
For all installations where a meter has not been previously installed and for new or replacement SPD/MPD installations, the fuse assembly installed must not be rated less than 100 amps.
The Australian and IEC standards require that a fuse assembly be marked with its rated current, i.e. if marked as 100 amps, rated current is 100 amps.
Service protection device (SPD) and/or meter protection device (MPD)
Clause 1.12.11 of the SIR and Clause 1.3 of the Annexure to the SIRs has the requirements for alterations, additions and upgrades.
It is now a requirement that the SPD and/or MPD meet the requirement of an HRC fuse or circuit breaker as per clause 2.8 wherever an alteration, addition or upgrade to service lines, service equipment or metering is undertaken.
For metering works it is not a requirement, under clause 1.3, for the fuse assembly to be rated at 100 amp unless the fuse assembly requires replacement, therefore existing service fuses fitted with an 80 amp or less HRC cartridge will meet the requirements of this clause and will not require upgrading.
Contact Electrical Compliance Team
This advisory note has been approved for issue by the Electrical Compliance Team.
Information contained within this document is current at the time it was last updated and refers to codes and standards current at the time of writing.
Building Commission NSW disclaims any liability (including for negligence) to any person in respect of anything done, or not done, by that person in whole or partial reliance on any of the information in this advisory note.
For more information, please email: electricalcompliance@customerservice.nsw.gov.au