Switches and sockets in wet areas
This advisory note outlines common non-compliances found by Building Commission NSW when inspecting electrical installations. It provides guidance to help licensed electricians and contractors carry out safe and compliant installations.
| Note | 2/2021 |
| Last updated | August 2025 |
| For | Licensees / Contractors / the Electrical Industry |
| Issued by | Building Commission NSW – Electrical Inspections Team |
| Scope | Applies to all of NSW |
Purpose
The purpose of this advisory note is to inform industry of some common noncompliances found when Building Commission NSW inspectors conduct inspections of electrical installations.
Reference
AS/NZS 3000:2018 Wiring Rules
What is the non-compliance?
Switches and socket outlets installed within wet (Zone 2) areas in bathrooms, laundries and kitchens.
Clearances to exclude switches and socket-outlets from the wet (Zone 2) areas are not calculated accurately. Switches within the wet (Zone 2) area do not have a minimum degree of protection of IPX4.
How to comply
As per the requirements of AS/NZS 3000 Wiring Rules:
- Table 6.1 outlines requirements where switches and socket-outlets may be permitted for installation.
Table 6.1: Selection and installation of electrical equipment for baths, showers and other fixed water containers
| Equipment | Zone 0 | Zone 1 | Zone 2 | Zone 3 |
|---|---|---|---|---|
| Clause 6.2.4.2 - socket outlets | Not permitted | Not permitted | (a) A shaver outlet; or (b) RCD-protected and in a cupboard (no specific IP rating). | (a) <0.3 m not permitted (b) ≥0.3 m no IP rating but shall have:
|
| Clause 6.2.4.3 - switches / accessories | Not permitted | Not permitted | < 0.3 m not permitted ≥ 0.3 m IPX4 | < 0.3 m not permitted ≥ 0.3 m - no IP rating |
- Fig 6.13 and 6.14 below outlines Zone 2 clearances for water containers that have a capacity of < 40L and > 40L.


- Fig 6.8 and 6.11 below outline Zone 2 clearance for a shower with a barrier and hinged door.


- Fig 6.1 and 6.2 below outline Zone 2 areas for baths.


What we are finding
On numerous inspections, switches and socket-outlets are located within the restricted zones created by sinks, showers, baths and laundry tubs and switches do not have the required minimum degree of protection of IPX4. Common non-compliances are illustrated in the following photos.

Example 1
Consider excluding the switch from the Zone 2 area by having a clearance of 0.6m from the bath (see Figure 6.1 AS/NZS 3000:2018) or the switch to be installed with a minimum degree of protection of IPX4.

Example 2
Consider excluding the switch from the Zone 2 area by having a clearance of 0.15m from the side of the basin and a clearance 0.4m from above the basin (see Figure 6.13 AS/NZS 3000:2018) or the switch to be installed with a minimum degree of protection of IPX4.

Example 3
Consider excluding the switch from the Zone 2 area by having a clearance of 0.6m from the shower screen entry (see Figure 6.8 AS/NZS 3000:2018) or the switch to be installed with a minimum degree of protection of IPX4.

Example 4
Consider excluding the socket-outlet from the Zone 2 area by having a clearance of 0.15m from the side of the basin and a clearance 0.4m from above the basin (see Figure 6.13 AS/NZS 3000:2018).
Contact Electrical Compliance Team
This advisory note has been approved for issue by the Electrical Compliance Team.
Information contained within this document is current at the time it was last updated and refers to codes and standards current at the time of writing.
Building Commission NSW disclaims any liability (including for negligence) to any person in respect of anything done, or not done, by that person in whole or partial reliance on any of the information in this advisory note.
For more information, please email: electricalcompliance@customerservice.nsw.gov.au