Temperature requirements for heated water installations
This advisory note explains the maximum delivery temperature requirements for heated water installations in NSW. It provides practical guidance for licensed plumbers and contractors installing, replacing, repairing or altering heated water services.
| Note | 3/2026 |
| Date issued | July 2026 |
| Last updated | September 2026 |
| For | Licensees, contractors, the plumbing and drainage industry |
| Issued by | Building Commission NSW, Practitioner Compliance, Plumbing Team |
| Scope | Applies to all of NSW |
This advisory note supersedes 'Installation requirements of temperature control devices' (1/2013).
Purpose
This advisory note supports licensed plumbers and contractors to understand the temperature requirements for heated water installations in NSW.
It explains the maximum delivery temperatures for fixtures used for personal hygiene, such as showers, baths, handbasins and bidets, and when a temperature control device must be installed under the Plumbing Code of Australia 2022.
The guidance applies when installing, replacing, repairing or altering heated water services and should be read with the relevant requirements in AS/NZS 3500.4:2021.
Issue
Building Commission NSW has identified a need to reinforce industry awareness of the temperature requirements for heated water installations in NSW, including clarification of circumstances where a temperature control device is required.
References
Code requirements for scald prevention
Part B2, Heated water services of NCC Volume Three, the Plumbing Code of Australia 2022 (PCA) sets out the requirements for any part of a heated water service of a property.
Performance Requirements
B2P2 Scald prevention (B2P2)
Heated water supplied by a heated water service must be delivered from the point of discharge of fixtures and appliances at a temperature that is unlikely to scald.
B2P2 applies to fixtures and appliances used primarily for personal hygiene, including showers, baths, handbasins and bidets.
How to comply with the scald prevention requirement
Any work to install, alter, or repair a heated water service within a property in NSW must comply with the current adopted version of PCA 2022.
The maximum delivery temperature requirements and heated water temperature control provisions are indicated in the PCA 2022. The clauses relating to sanitary fixture delivery temperatures and methods for controlling delivery temperatures no longer appear in AS/NZS 3500:4:2021.
The relevant Deemed to Satisfy Provisions in the NSW variations to Part B2 of the PCA are NSW B2D5: Maximum delivery temperature and NSW B2D6: Temperature control devices.
NSW B2D5: Maximum delivery temperature
The delivery temperature of heated water at the outlet of each sanitary fixture must be:
- Not more than 45°C in any:
- residential part of an aged care building; or
- patient care area in a health-care building; or
- part of an early childhood centre, or primary or secondary school, that is used by children; or
- any facility designated for use by people with a disability; or
- Not more than 50°C in all other cases.
B2D5 applies to all heated water installations for personal hygiene purposes.
NSW B2D6: Temperature control devices
- A temperature control device used to delivery heated water in accordance with B2D5(a) must be a:
- thermostatic mixing value; or
- thermostatically controlled tap.
- A temperature control device used to deliver heated water in accordance with B2D5(b) must be a:
- thermostatic mixing valve, or
- thermostatically controlled tap; or
- tempering valve; or
- temperature limited water heater with a maximum delivery temperature of 50°C marked in accordance with AS 3498.
- The required maximum delivery temperature must be achieved in accordance with AS/NZS 3500.4.
When does B2D6 apply?
- All new heated water services; or
- Replacing a hot water heater, regardless of the type or location of the heater.
Exemption for manifold water heaters
A temperature control device need not be installed if one or more, but not all, heating units in a manifold water heater are replaced.
Regulatory commentary
The following table provides guidance on when a temperature control device is required for common types of heated water services work.
| Heated water work undertaken | Temperature control device required | |
|---|---|---|
| 1 | Installing a water heater for premises for the first time | Yes |
| 2 | Replacement of an existing heater with a like-for-like water heater | Yes |
| 3 | Replacement of an existing heater with an alternate model, size or heat source | Yes |
| 4 | Repositioning of an existing heater to a new location | Yes |
| 5 | Replacement of any associated valves, elements thermostats etc Excludes the replacement of any existing temperature control device | No |
| 6 | Replacement of a heater unit where currently a touch pad temperature control unit is installed | Yes |
| 7 | Altering or extending an existing heated water service to serve additional sanitary fixtures but no work is carried out on the existing heater and there is no existing temperature control device installed Only the new sanitary fixtures are required to have tempered water supplied, although the entire system may be tempered. | Yes |
| 8 | Replacement of an existing plumbing fixture or fitting and there is no existing temperature control device Example: replacement of a basin tap | No |
| 9 | Replacement of all fixtures within an existing bathroom and the existing heated water supply has no temperature control device installed Only the replaced sanitary fixtures are required to be tempered but the whole of system may be tempered Note: Applies to bathroom renovation including the replacement and or repositioning of fixtures and fittings | Yes |
| 10 | Replacement of solar collection panel only | No |
| 11 | Replacement of all of the heaters that are installed in an installation consisting of multiple heaters, typically known as a bank or manifold of heaters. Scenario: there are 6 heating units in a bank or manifold of water heaters. Example: all 6 heating units are replaced at the same time | Yes |
| 12 | Replacement of one or more heaters, but not all of the heaters in an installation consisting of multiple heaters, typically known as a bank or manifold of heaters. Refer to ‘Exemption for manifold bank of water heaters’ - NSW B2D6 | No |
Contact Practitioner Compliance Team
This advisory note has been approved for issue by the Practitioner Compliance Team.
Information contained within this advisory note refers to codes and standards current at the time it was last updated.
Building Commission NSW disclaims any liability (including for negligence) to any person in respect of anything done, or not done, by that person in whole or partial reliance on any of the information in this advisory note.
For more information, please email the Practitioner Compliance Team.