Tundish installation
This advisory note outlines the general installation requirements when connecting tundishes.
| Note | 14/2021 |
|---|---|
| Date issued | July 2021 |
| Last updated | July 2021 |
| For | Licensees / Contractors / the Plumbing and Drainage Industry |
| Issued by | Building Commission NSW Building Specialist Compliance Unit |
| Scope | Applies to all metropolitan and regional areas in NSW |
Issue
During recent audits of Class 2 buildings by the Building Commission NSW Building Specialist Compliance Unit (BSCU), tundish installations are frequently installed in a non-compliant manner.
The following advisory note has been prepared to remind the industry of the general installation requirements regarding the connection of tundishes set out in AS/NZS 3500 Part 2, clause 13.21. Some additional referenced clauses have been listed to further help clarify the connection of tundishes to floor wastes.
Detail
13.21 Connection of tundishes
Considering AS3500.2, here are 3 common non-compliances related to tundish installations serving a condensate line that have been observed:
Non-compliant example 1

Installation does not comply with AS3500:2 c.13.21
Non-compliant example 2

Installation does not comply with AS3500:2 c.4.6.7.3, c.13.21
Non-compliant example 3

Installation does not comply with AS3500:2 c.4.6.7.3, c.6.5.1, c.13.21
4.6.7.2 Discharge to floor waste gullies
Table 4.6.7.2: Discharge to floor waste gullies
Waste fixture | Maximum length of waste pipe m | ||
|---|---|---|---|
| Connected to riser of floor waste gully | Connected to submerged inlet floor waste gully (see Figure 4.6.7.2) | ||
| Fixture untrapped | Fixture trapped | Fixture trapped or untrapped | |
| Tundish (see Clause 4.6.7.8) | 10.0 | 10.0 | 10.0 |
Note: Floor waste gullies or similar traps directly connected to the drainage system and subjected to infrequent use shall be provided with an approved means of maintaining their water seals.
4.6.7.3 Connection of fixtures
4.6.7.8 Discharges from tundishes
It is important to also note the clause and table excerpts from AS3500:2. Some examples of compliant installations are shown below:
Compliant example 1

Compliant example 2

Compliant example 3

Compliant example 4

Compliant example 5

Compliant example 6

6.5.1 General
Information contained within this advisory note refers to codes and standards current at the time at when it was last updated.
Building Commission NSW disclaims any liability (including for negligence) to any person in respect of anything done, or not done, by that person in whole or partial reliance on any of the information in this advisory note.